Abstract

ABSTRACT Aside from climatic parameters, the cooling potential of a desert cooler is influenced by fan flow rate, pad thickness, and pad packing factor, all of which are referred to as cooler parameters. In this study, a general equation for determining cooling potential in terms of cooler parameters is proposed and validated. An equation has been devised to determine the combination of fan flow rate (FFR) and pad area required to meet a given heating load. The equation aids in the sizing of coolers for a desired room temperature in various climates. The size of the cooler tank is determined by the rate of water evaporation. In this investigation, we evaluated the influence of different fan flow rates on the rate of water evaporation. It is seen that at a typical set of climatic parameters and for a given pad (1 m2, 350 m2/m3, 10 cm thick), the cooling potential of the cooler increases by increasing fan flow rate (. Furthermore, increasing pad area reduces the amount of fan flow rate required for a given heating load, allowing one to select the appropriate combination of fan flow rate and pad area. Higher fan flow rates increase the running cost, while increasing pad area raises the initial investment cost. The pad area needed (10 cm, 350 m2/m3) for the composite climate of Delhi at a 0.35 m3/s FFR, is roughly 66.7% less than that for the hot climate of Jodhpur for 4 kW heating load.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.