Abstract

Resonance or harmonic amplification occurs when the frequency of the harmonics generated by the converter station is near the inherent resonance frequency of the substation. Considering there are six DC projects in the Yunnan power grid, analysing the resonant characteristics of the grid is imperative for safety reasons. This study establishes a simulation platform of the Yunnan power grid based on the Power System Analysis Software Package and formulates the modelling principles and simulation steps. In order to successfully analyse the resonant characteristics of a substation under normal operation mode and put forward any necessary suggestions, the impedance frequency of all 500 kV substations in the power grid are scanned. This is followed by studying, the influence of different operation modes of Yunnan power grid and different operation modes of DC system of Luxi converter station on the resonant characteristics of Yunnan substation. Based on these results, effective measures for resonance suppression are proposed.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.