Abstract
The authors of this paper proposed an effective method applied to frequency response interpretation in low frequency range and mechanical failure diagnosis support based on measurements and analysis of a physical lumped component transformer circuit. To extend the interpretation until medium frequencies where mechanical failures influence most, this paper presents a novel approach on determining parameters in a physical distributed component circuit. The most important contribution of this paper is the possibility of determination of electrical parameters in the distributed circuit without knowing detailed knowledge of the transformer construction, which has been a challenge so far. In addition, the application capability of the distributed circuit in diagnosis of several mechanical failures in a distribution transformer is also investigated.