This paper describes the bypass circuit design applied to International Thermonuclear Experimental Reactor (ITER) poloidal field converter system. In the baseline design, an internal bypass scheme was designed for purposes of quench protection and reactive power reduction by bypass operation. However, due to the potential risks that exist in case of fault protection, internal bypass scheme is abandoned finally and external bypass scheme is proposed to replace the internal bypass design. In this paper, the weakness of internal bypass design has been reviewed and the reliability of external bypass design at different sites is analyzed. Simulations based on SIMULINK are performed to confirm the reasonability and availability of external bypass proposals.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.