Abstract

Sequential control applied to the International Thermonuclear Experimental Reactor (ITER) poloidal field converter system for the purpose of reactive power reduction is the subject of this investigation. Due to the inherent characteristics of thyristor-based phase-controlled converter, the poloidal field converter system consumes a huge amount of reactive power from the grid, which subsequently results in a voltage drop at the 66 kV busbar if no measure is taken. The installation of a static var compensator rated for 750 MVar at the 66 kV busbar is an essential way to compensate reactive power to the grid, which is the most effective measure to solve the problem. However, sequential control of the multi-series converters provides an additional method to improve the natural power factor and thus alleviate the pressure of reactive power demand of the converter system without any additional cost. In the present paper, by comparing with the symmetrical control technique, the advantage of sequential control in reactive power consumption is highlighted. Simulation results based on SIMULINK are found in agreement with the theoretical analysis.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.