Abstract
Industrial Ethernet is widely used in automation and control system because of its high reliability and good communication performance. There are several protocols for Industry Ethernet. In different applications, it is necessary to select a appropriate protocol standard according to different needs. In order to apply industrial Ethernet in the active surface system of QTT, the control network requirements of active surface system were summarized. The period and jitter of three protocol standards, Ethernet/IP, Profinet RT and EtherCAT, were tested by evaluation hardware. The differences between network configuration and ring redundancy settings are analyzed. The results show that EtherCAT is more suitable for the network application requirements of active surface system of QTT.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.