Abstract

AbstractHigh‐frequency oscillations in voltage transformers are analyzed by the FFT method, using an equivalent lumped circuit. Such an analysis has been regarded as difficult because the transformers used in high‐voltage distribution systems have a large number of turns. The constants of the equivalent circuit are evaluated on a turn‐to‐turn basis. The frequency domain analysis is followed by time domain analysis using the FFT technique. Both characteristics are verified by an experiment on a 6.6‐kV voltage transformer. The nature of the high‐frequency oscillation is shown for a simpler model. It is found that the interlayer voltage becomes highest at the entrance to the incoming surge. © 2008 Wiley Periodicals, Inc. Electr Eng Jpn, 163(1): 8–15, 2008; Published online in Wiley InterScience (www.interscience.wiley.com). DOI 10.1002/eej.20643

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.