Abstract
In this paper analysis of common mode voltage or neutral shift in the new emerging voltage source inverter type medium voltage adjustable speed drive (MV-ASD) systems is presented. Both cascaded multi-level (CML) inverter and 3-level NPC inverter topologies are analyzed. An equivalent circuit model to determine the common mode voltage stress is presented. Analysis and simulation results are discussed and worst case common mode voltage excursion is computed for an example 800 HP, 4160 V MV-ASD. It is shown that certain system components are excessively stressed and in the MV-ASD system these data are particularly useful in specifying system components and for proper design of the system. Possible effects of common mode voltage and its dv/dt on medium voltage motor bearings are discussed. A new. Multi-level PWM strategy is introduced which results in zero common-mode voltage. Simulation results are shown to illustrate the effectiveness of these schemes, Finally, experimental results from a 800 HP, 4160 V, MN-ASD system are presented.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.