Abstract

When dry-type air-core reactors are in operation, the surrounding grounding devices, fences and other closed structural parts are abnormally hot. Because there is no effective analysis and detection methods for concealed projects such as grounding devices, it brings great difficulties to on-site analysis of problems; this article is based on the site conditions Theoretical analysis and the use of ground penetrating radar detection technology to study a 66kV dry-type reactor grounding device abnormal heating problem, through the analysis of the detection results, it is found that the reason for the heating of the dry anti-grounding device is that the grounding device has a circulating current in the alternating field; The design and construction of grounding devices of dry-type air-core reactors in new projects will provide certain reference significance.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.