Abstract
Disruption to the transfomator can result in losses that disrupt the flow of electricity toconsumers. Harmonics are disturbances that arise due to the operation of non-linearloads. The purpose of this study is to analyze the efficiency of the KA4214 transformerat the Udayana Bukit Jimbaran Engineering Faculty with harmonics, namely the R =16.9%, S = 13.8% and, T = 16.1%. . The method used is to simulate and analyze withthe results of harmonic measurements in existing conditions, active filters, and activefilters based on fuzzy logic controller using Matlab software. The optimal resultsobtained are using the fuzzy logic controller method with the results of R = 0.85% S =0.65% T = 0.39% and the efficiency results are 99.99%.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.