Abstract
Phasor Measurement Unit (PMU) is considered to be the most significant device in future power system measurements. It provides phasor information (both magnitude and phase angle) which can be used in the real time control of power systems. In this paper, optimal PMU placement problem (OPP) is articulated as a binary integer linear programming (BILP) using Balas additive algorithm (BAA). PMU installations will be decided by binary decision variables (0, 1) for full network observability while minimizing the number of PMU installations. Existence of zero injection buses was also considered to reduce the number of PMUs used for observability. Power system connectivity matrix represented in binary form and simple heuristics are used to solve the problem. Optimal PMU placement problem has multiple solutions with equal costs. For further ranking of these multiple solutions measurement redundancy is used. The proposed algorithm has been tested on IEEE 9-bus, 14-bus, 24-bus, 30-bus systems.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.