Abstract

A new interphase distance relaying algorithm for series-compensated transmission lines is proposed in this paper. The fault impedance can be correctively calculated using the proposed algorithm without requirement of the parameters of series capacitor device. The series capacitor can be simplified as a linearized impedance during the fault period, but its parameters can be used as variables in fault loop equations. The real-time digital simulator tests show that the proposed algorithm can obtain more accurate results than other traditional distance relaying algorithms for series-compensated transmission lines.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.