Abstract

A new distance-relaying algorithm for single-phase-to-ground faults on series-compensated parallel transmission lines is proposed in this article. Fault impedance can be calculated using this algorithm without any parameters requirement of mutual coupling and series capacitor device (series capacitor/metal oxide arrestor/discharging gap). The series capacitor device is simplified as linearized impedance during faults. The parameters of mutual coupling and a series capacitor device can be used as variables in the fault loop equations. Real-time digital simulator tests show that the proposed distance-relaying algorithm can obtain more accurate results than traditional distance-relaying algorithms for series-compensated parallel transmission lines.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.