Abstract
This paper proposed an improved thermal-circuit model for power transformer hot-spot temperature prediction with dynamic loading. The influences of solar radiation and the environmental temperature on the heat dissipation were also considered. When calculating the heat dissipation from the transformer tank to surroundings, the average oil temperature was selected as the node value in the thermal circuit. The new thermal models will be validated with the delivery experimental data of a 220kV-300MVA unit and a 220kV-75MVA unit.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.