Abstract
The feasibility of increasing operating capacity of existing power transformers is studied based on a novel dynamic thermal circuit model in this paper. Hot-spot temperature of a transformer is the most important parameter to determine the operation capacity. However, only top-oil temperature is monitored and hot spots usually appear at windings. In this paper, a dynamic thermal circuit model considering environment factors and operation conditions is established. To implement and verify the dynamic thermal circuit, the real-time loss and cooling thermal resistance of the transformer is calculated firstly. And then hot-spot temperature based on the average oil temperature is calculated for a period of 24 hours. The calculated result is compared with the measured temperature data under the same conditions. The comparison shows that the accuracy of the proposed model is satisfactory. The proposed model is then used to evaluate the feasibility of increasing operating capacity. The evaluation indicates that the continuous operating capacity can be increased. After capacity increased, the transmission energy can increase remarkably, while the service life is reduced lightly.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.