Abstract

This paper presents a phase-locked loop less (PLL-less) control scheme (PLCS) with an improved proportional resonant (IPR) controller for a grid-tied solar photovoltaic system (GTPVS). The proposed control scheme operates in a self-synchronized mode without the need of a PLL block. This reduces the computational burden on the controller and eliminates the delay due to the PLL block. In addition, it also improves the dynamic performance of the GTPVS under grid frequency deviations. The improved proportional resonant (IPR) controller reduces grid current harmonics under distorted grid voltages. Further, this control scheme is utilized to eliminate the active and reactive power ripples during grid fault or sag conditions. In order to extract the maximum power from photovoltaic (PV) array, a variable step-size incremental conductance (VSS-INC) maximum power point tracking (MPPT) algorithm is implemented. Real-time experiments are carried out using OPAL-RT real-time simulator to verify the effectiveness of the proposed PLCS compare to the conventional PLL-based control scheme (PBCS).

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.