Abstract

High-voltage flexible power systems, with their intrinsic characteristics, play an increasingly important role in electronic power systems. Synchronization between the inverter and the grid needs to be achieved by a phase-locked loop (PLL), the performance of which determines the quality of power transmission. This paper proposes a PLL adapted to extremely harsh grid conditions. Firstly, the traditional synchronous reference frame PLL and the dual second-order generalized integrator (DSOGI-PLL) are analyzed, and the errors in phase-locking and the shortcomings of these two methods in the presence of DC components in the grid are pointed out. Secondly, based on the harmonic grid voltage, a repetitive control internal model is introduced by DSOGI to realize the real-time tracking and regulation of the harmonic signals in order to suppress the harmonic voltage disturbance. In addition, a DC bias elimination and frequency adaptive method is proposed to solve the problems of DC bias and grid voltage frequency fluctuation in order to achieve adaptive tracking of the grid phase. Finally, the superiority of the proposed strategy is verified through simulations and experiments.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call