Abstract

The technology proposed in this study aims to improve the performance characteristics and coefficient of performance (COP) of a geothermal system by fundamentally preventing underground water discharge and maintaining a constant temperature of the underground heat exchanger composed of bleed discharge water that utilizes two balancing wells using cross-mixing methods. The results of the cooling and heating operations of the existing standing column well (SCW) and the balancing well cross-combined heat exchange systems show that the measured COP increases by 23% during the cooling operation and 12% during the heating operation. When operating with a balanced well-cross-mixed heat exchange system, the initial temperature of the underground is constant with a small standard deviation of 0.08–0.12 °C. The results of the measured values using this technology show that, if the operational method is changed from the ordinary SCW-type heat exchange system to a balanced well-intersected heat exchange system, the COP of the cooling and the heating system using geothermal heat not only improves but also ensures a stable supply of geothermal sources by maintaining a constant initial temperature. This finding is useful to fundamentally eliminate the ultimately wasted bleed water.