Abstract

An experimental study of the pressure drop under subcooled flow boiling of the refrigerant R141b in a system with two slotted microchannels was carried out. A copper block with two microchannels 2 mm wide, 0.4 mm deep, and 16 mm long was used as an experimental section for testing. The mass flow rate varied in the range from 1 to 4 g/s, the initial subcooling from 20°C to 50°C. Experimental data show a significant decrease in the pressure drop when the critical heat flux is reached. The experimental data are compared with the model known from the literature. Experimental data show that the occurrence of nucleate boiling incipience at subcooled boiling corresponds to a larger heat flux than that given by the recommended correlation.