Abstract

In this paper, a multi-purpose hybrid desiccant integrated vapor compression air conditioning system of a small capacity is experimentally investigated. The system, referred as HDAC, is designed to meet the cooling load of spaces having large latent heat portions and at the same time to extract water from atmospheric air. The system is mainly consisted of a liquid desiccant dehumidification unit integrated with a vapor compression system (VCS). The dehumidification unit uses lithium chloride (LiCl) solution as the working material. The effect of different parameters such as, desiccant solution flow rate, process air flow rate, evaporator and condenser temperatures, strong solution concentration and regeneration temperature on the performance of the system is studied. This system has a water recovery rate of 6.7 l/h.TR of pure water at typical north Egyptian climate. The HDAC system has a COP as high as 3.8 (an improvement of about 68% over the conventional VCS. The system offers a total cooling capacity of about 1.75 TR using a 0.75 TR VCS unit. Finally, the proposed system is found to have a payback time of about 10 months without any considerable extra capital cost compared to the known split air conditioning system. The results emphasize the potential benefits of the HDAC system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.