Abstract

Analysis of borehole thermal resistance is important for the standard sizing of ground heat exchanger (GHE). In this paper, a p-linear dimensionless average fluid temperature is proposed to estimate borehole thermal resistance. A p-linear dimensionless fluid temperature and p-linear dimensionless average fluid temperature are introduced, and the p-linear dimensionless fluid temperature is compared with theoretical dimensionless fluid temperature calculated by quasi-three-dimensional model for both single and double U-tubes. Results show that the p-linear dimensionless temperatures with parameters p→0 and p=−1/2 are respectively in good agreement with the theoretical dimensionless fluid temperatures of single and double U-tubes. Therefore, the dimensionless logarithmic mean temperature for p→0 and the dimensionless geometric mean temperature for p=−1/2 should respectively be adopted to reasonably estimate the thermal resistance of single and double U-tube boreholes.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.