Abstract
The optimum dielectric design of gas circuit breakers (GCB) in a consistent design philosophy is described. Many electric field calculations were carried out on 3 GCB models and the relation between the key design parameters such as distance between tank and shield, major radius of shield electrode and full open distance were analyzed. As a result, it was found that there is a minimum curve in the relation between full open distance and the electric field strength. Using this minimum curve and the allowable electric field strength, we can design the optimum GCB structure. It is also shown, as an example, how to design the optimum GCB of 300 kV by using 3 GCB models.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.