Abstract

In case of unintentional islanding, distributed generation units must be able to detect it and disconnect from the grid in less than 2 seconds. In this work, a Rate of Change of Frequency (RoCoF) method has been developed for islanding detection. Since these algorithms are conditioned by the requirements of grid codes, ENTSO-E network code and IEC 62116 have been taken into account. The RoCoF anti-islanding algorithm has been developed in MATLAB-Simulink and implemented through rapid prototyping techniques in an FPGA ALTERA Cyclone V. To check the proposed protection algorithm, simulation tests have been carried out. Finally, the RoCoF anti-islanding protection has been validated using FPGA in the loop and experimentally in a real 20- kW inverter.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.