Abstract
All distributed-generation units need to be equipped with an anti-islanding protection (AIP) scheme in order to avoid unintentional islanding. Unfortunately, most AIP methods fail to detect islanding if the demand in the islanded circuit matches the production in the island. Another concern is that many active AIP schemes cause power-quality problems. This paper proposes an AIP method which is based on the combination of a reactive power versus frequency droop and rate of change of frequency (ROCOF). The method is designed so that the injection of reactive power is of minor scale during normal operating conditions. Yet, the method can rapidly detect islanding which is verified by PSCAD/EMTDC simulations.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.