Abstract

Over the years, high voltage transmission of large energy blocks over long distances has widely developed from the Line Commutated Converter (LCC) technology. However, the continuous expansion of the AC network and the increase in renewable energy penetration leads to the weakening of Electric Power Systems (EPS), causing operational problems for the LCC-HVDC. This paper evaluates the degree of contribution of the VSC-HVDC on the LCC-HVDC dynamic performance when the infeed is in a hybrid multi-infeed HVDC system. Through a steady-state mathematical framework, the new concept of Hybrid Power Voltage Interaction Factor (hPVIF) is proposed to assess the transient stability improvement of LCC. Additionally, this article introduces two key contributions from hPVIF: the complementary Improved Commutation Failure Immunity Index (iCFII), as a measure of the effective short circuit enhancement, as well as the apparent line length, which emulates the line lengths adjusting the power dispatch in the VSC-HVDC. PSCAD/EMTDCTM time-domain dynamic simulations are performed to assess the indexes, and the Matlab® software will be used to assist in mathematical operations.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call