Abstract

Evaporation of liquid ammonia distributed by commercial spray nozzles onto a horizontal low-fin steel tube of 3/4 in. diameter was tested. Experiments were conducted for the average local spray flow rate from 0.0139 kg/(s{center_dot}m) to 0.0788 kg/(s{center_dot}m), saturation temperature from {minus}23.3 C to 10 C, and heat flux from 10 kW/m{sup 2} to 80 kW/m{sup 2}. The effects of heat flux, saturation temperature, spray flow rate, and nozzle height were investigated. Both standard-angle and wide-angle commercial nozzles were tested. The Nu data were correlated as a function of Re, Pr, and reduced pressure, and heat flux. The heat transfer coefficient data of the low-fin tube are compared with those of a corrugated tube and plain tube.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.