Air leakage measurements by the tracer dilution technique were performed in five military aircraft hangars. The hangars were located in regions of the country having diverse weather characteristics. In several of the hangars, distinct measurements were performed to assess the degree of homogeneity of the air-tracer gas mixture in these large volume structures. Air leakage rates in the range of 0.6 to slightly above 2.0 air changes per hour (ACH) were measured. Surprisingly, these values do not differ significantly from those which might be measured in single-family residences. Since, in use, aircraft hangars often have at least one sliding door open, tracer dilution measurements were performed to show the increase in air leakage to be expected with one and two (oppositely located) doors open.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.