This paper describes the capabilities and mathematical basis of an advanced fault analysis program. This program handles simultaneous unbalanced fault analysis with detailed treatment of shunt branches, off-nominal transformers, and loading conditions as given by a base case load flow solution. Provision is made for large groups of branches with common mutual coupling. The program uses the diakoptic (piecewise) solution method to allow each sequence network to be handled independently, even though they are effectively interconnected by unbalanced faults. Efficient computer implementation is based on the optimally ordered triangular factorization of the individual sequence admittance matrices within the diakoptic procedure, and an efficient iterative method of handling mutual couplings.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.