Abstract

In this article, an improved grid synchronization method for three-phase grid-feeding converters using a dual enhanced second-order generalized integrator (eSOGI) frequency-locked loop (FLL) is proposed. The eSOGI, of which gains can be adjusted based on the positive-sequence component of the grid voltage, is designed to estimate the grid voltage accurately. Moreover, to improve the grid frequency estimation under grid voltage sags, frequency rate limits is suggested in the FLL structure. The selection of the eSOGI-FLL parameters is described as well. After the estimated grid voltages are obtained using the dual eSOGI-FLL, they are used to synthesize the references in the dual-current controllers for positive- and negative-sequence components. Through the simulation and experimental results under grid voltage sags and distorted grid conditions, the improved power control performance of the proposed method has been demonstrated in comparison with those of the existing methods.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.