Abstract
As partial discharge (PD) monitoring has become a significant means of insulation fault diagnosis, built-in UHF sensors is increasingly adopted in GIS. In this letter, we report a hypersensitive triple-band optical PD sensor which is combined to a UHF sensor with an existing flange assembled on GIS. By experiments performed on an 110 kV GIS chamber, it demonstrates that with the spectral information obtained by this novel optical sensor, the discharge severity evaluation and the multi-source discharge clustering can be realized without any signal strength and phase-resolves statistics, which has a practical significance for the fault diagnosis of HVDC equipment such as DC GIL and DC bushing.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.