Abstract

This paper proposes an emergency load shedding scheme aimed at stopping a developing voltage instability before system disruption. The proposed scheme has a wide-area view of the system, adapts itself to the emergency situation to be handled, and works in closed-loop. It relies on the detection of voltage instability from synchronized measurements recently proposed by the authors. It inherits the assumptions of this detection method (availability of a rich phasor measurement set and communication infrastructure). The method is adaptive in so far as the voltage thresholds used by this undervoltage load shedding scheme are determined from the measurements of the system evolution itself, and the curtailed power is adjusted to the severity of the situation. The features of the proposed scheme are illustrated on a small but realistic system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.