Abstract
The LCL filter is widely applied as interface between grid-connected inverter and grid due to the preferable high frequency attenuation characteristic. Under the condition of weak grid, impedance value of grid model cannot be ignored, the existence of grid impedance results in different LCL resonant frequencies, which will arise challenges of traditional active damping control. Based on the analysis of band pass filter using active damping control strategy, an adaptive active damping control is proposed in this paper by introducing the application of active notch filter, which can adjust the position of negative resonance point adaptively so as to manage sudden grid changes. Theoretical analysis and simulation results presented on the platform of grid-connected PV inverter system indicate the effectiveness and adaptability of this active damping strategy.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.