Abstract

As typical representatives of converter-interfaced sources with four quadrant operation capability, battery energy storage station (BESS) and VSC-HVDC station behave differently with synchronous generator. This leads to the high risk of incorrect operation of current differential protection (CDP), seriously threatening the security of transmission network. Motivated by this issue, this paper presents adaptive additional current-based differential protection (AAC-DP). Adaptive additional current is introduced to modify the criterion of current differential protection. Ulteriorly, the unified expression of adaptive additional current for internal and external faults is designed. Adaptive additional current can increase the sensitivity during internal fault, whereas it improves the security during external fault. The sensitivity and dependability of AAC-DP was widely evaluated by changing operation mode, fault condition, and type of power source using PSCAD and RTDS-based experimental platform. Also, the adverse factors, such as saturation and error of current transformer(CT), and noise, were taken into account; thereof, the excellent security of AAC-DP was confirmed. The results confirm that AAC-DP exhibits excellent performance in operating speed, sensitivity, the adaptation to fault behaviors of BESS and VSC-HVDC, and robustness against saturation and error of CT, and noise.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.