Abstract
AbstractSystematic studies on the across‐wind dynamic interference effects on two and three tall buildings are presented in this paper. It is found that surrounding and upstream interfering building(s) can significantly affect the across‐wind load on the interfered principal building. Generally speaking, two interfering buildings can cause more adverse dynamic effects on the principal building than a single one does. The results show that the maximum interference factor (IF) among three buildings increases 80% over that between two buildings in terrain category B which has been defined in Chinese load code for design of building structures; a noticeable difference of 29% of IF is also observed in terrain category D. Vortex shedding from the upstream buildings can lead to vortex‐induced resonance, resulting in excessive across‐wind loads on the downstream building. Although interference effects in terrain category D are much smaller than those in exposure category B, the maximum IF is found to be 1·83 in the case of three buildings with the same size in terrain category D and 2·27 in other configurations. Copyright © 2007 John Wiley & Sons, Ltd.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: The Structural Design of Tall and Special Buildings
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.