Abstract

Abstract This paper presents a new wavelet-based negative-phase sequence (unbalanced currents) protection scheme for synchronous generators. The scheme utilizes the three line voltages and the three line currents available at the generator terminals. Wavelet transform concept is presented. The principle of operation of the algorithm is introduced. Feature extraction technique is derived. Data window necessary for the algorithm is ten samples based on 1200 Hz sampling frequency. Generated data from the simulation of a model power system using emtp were used in the matlab software to test the performance of the technique. The performance under different system conditions is discussed. The results show that the new approach provides robust and accurate classification for a variety of power system conditions.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.