Abstract

The sensitivity verification with the ultrahigh-frequency (UHF) method will be discussed in this paper. The sensitivity line with the UHF method based on the conventional (IEC 60270) one is different in the radial position of the defects inside gas-insulated substation (GIS), because transverse-electromagentic mode can be more weakened while transverse electric (TE)/transverse magnetic (TM) modes can be more enhanced as the defect comes close to the enclosure than the conductor. The result makes it difficult to detect the free particle with IEC 60270. A unique sensitivity verification, which is combined with real-time PD identification method, first enables us to identify the defects and thereafter to calibrate the apparent charge of each specified defect according to the sensitivity line.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.