Abstract

Using direct-tunable diode laser absorption spectroscopy, we obtained simultaneous oxygen, water vapor, and temperature measurements in situ during aqueous high expansion foam-suppressed fires in a foam-adapted cup burner apparatus. Foams with expansion ratios ranging from 55:1 to 129:1 were delivered at various rates; measurements were obtained 5.5 cm above and 1.5 cm outside the cup burner exit. By monitoring water vapor as foam advances through the cup burner chimney with and without the flame present, we are able to quantify evaporation due to the presence of the thermal and radiating field. We are also able to measure the impact on the oxygen concentration resulting from flame consumption of oxygen versus release of oxygen from evaporating foam bubbles. By analyzing video captured during each foam injection event, foam velocities during fire suppression and in the absence of the flame were measured.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.