A study has been undertaken to determine the shear behavior of reinforced concrete members in nuclear power plant facilities following sustained heating to high temperatures. A total of nine specimens was tested. The parameters of the tests were (1) heating temperature (65, 90 and 175°C) and (2) heating period (1, 3, 6 or 12 months). Different combinations of these parameters were employed, and the shear strength deterioration rate was evaluated. The test results were confirmed by a non-linear finite element analysis. The relationship between the concrete compressive strengths, which varied from heating face to upper portion, and the shear strength in specimens was evaluated.