Abstract

The experimental part of the study of the reverse cycle defrosting performance on a four-circuit outdoor coil unit in an experimental 6.5 kW heating capacity residential ASHP has been reported in Part I of a two-part series. The experimental results indicated that downwards flowing of the melted frost along a multi-circuit outdoor coil surface would have negative effects on defrosting performance. In order to quantitatively analyze the effects, this paper, the second part of the two-part series, reports on a modeling analysis where a semi-empirical model of the airside defrosting in the four-circuit outdoor coil unit was developed. The model was validated by comparing the predicted defrosting duration and temperature variation of collected melted frost with the corresponding experimental data presented in Part I of the two-part series. Using the validated model, the frost-melting rate and the temperature of melted frost on the surface of each circuit were predicted. The effects of the downwards flowing melted frost along the entire outdoor coil surface on defrosting performance were quantitatively analyzed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.