Abstract

To assess static voltage stability in power networks, critical load values were examined at each load bus as a voltage instability predictor. However, the information that is required to evaluate loadability conditions is usually not available at load buses. To predict impending voltage collapse in a droop-controlled power distribution network, this paper introduces a static voltage stability detector that only uses local measurements at generator buses. The local stability detector derives a voltage threshold from dynamics of each droop-controlled generator. Monte Carlo simulations are conducted in the IEEE nine-bus network to evaluate the detector's receiver operating characteristic (ROC). Simulations show that the local voltage stability detector has a better performance than loadability conditions in a stressed power distribution network with droop-controlled generators and requires much less information to implement.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.