Abstract

In this paper, a voltage harmonic injection method at the dc-link is proposed to reduce input current harmonics of the series-connected 12-pulse rectifier. The proposed method uses an auxiliary circuit to generate the voltage harmonics and injects the voltage harmonics into the dc link of the series-connected 12-pulse rectifier so that the input voltages of the 12-pulse rectifier can be shaped as 24 steps. The formation processes of the input voltage are analyzed based on the switching functions; and the turn ratio of injection transformer is optimally designed from the perspective of minimizing the total harmonic distortion (THD) of the input voltage. After using this method, experimental results show that the input voltages of the isolated transformer are 24-step waves with an experimental THD of around 3.34%; the input line currents of the proposed rectifier are close to sinusoidal waveforms with an experimental THD of around 2.65%. More importantly, the kVA rating of the injection transformer is only about 2.3% of the load power, which means that the cost of harmonic reduction is very low.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.