Abstract
Developing effective fault detection and diagnosis (FDD) model is of great significance to the energy efficiency and comfort of variable refrigerant flow (VRF) system. In recent FDD studies, the consideration of incomplete information and uncertainty, as well as the generalization of model and the interpretability of fault action mechanism have become a great concern. This paper accordingly proposes a fault diagnosis strategy based on attention-BiLSTM with ensemble feature sets. Three methods including Correlation Analysis, Information Entropy, and Gini Impurity are used for feature selection and ensemble feature sets combination. The proposed model can achieve interpretability of fault diagnosis and quantification of diagnosis uncertainties through attention mechanism and ensemble feature sets. A total of four typical faults under different working conditions are used to verify the accuracy and generalization of the proposed method. The results show that the ensemble attention-BiLSTM model has a fault diagnosis accuracy rate of 98.3% if the first two most likely outputs are considered, and when some sensors fail, the accuracy rate can still remain above 90%. In addition, a generalization verification idea is proposed, that is, the model is trained under specific operating conditions and tested on datasets with different operating conditions or fault levels. The results show that the average generalization of the optimized model reaches 86%.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have