Abstract

AbstractThis paper presents a simple and robust direct current control based predictive approach for rotor side converter (RSC) of the doubly fed induction generator (DFIG), which operates at a constant switching frequency and has a fast dynamic response. First, sector of required rotor voltage vector is predicted in this strategy, and according to this predicted sector, two active vectors and two zero vectors are elected in each switching period. Derivatives of rotor current in the synchronous frame are determined for each predicted voltage vector in every period. These derivatives are used to compute the duration of the vectors in such a way that the current error at the end of the switching period gets minimized. The accuracy of the proposed control strategy under variation of rotor speed is evaluated in Matlab/Simulink environment for a 2 MW DFIG. Moreover, the impact of parameter variations on the system is examined for this suggested technique. Furthermore, the dynamic response and stator current total harmonic distortion (THD) of proposed strategy is compared with traditional vector control (VC), direct power control (DPC) and predictive direct power control (PDPC) methods. Finally, the performance of the proposed method is evaluated under disturbance voltage. The results demonstrate that suggested control technique has the lowest stator current THD and operates perfectly near the synchronous speed and under grid voltage dip. Copyright © 2015 John Wiley & Sons, Ltd.