Abstract
This paper presents a validation of a real-time digital simulation of a transmission line model with frequency dependent parameters, The real-time transmission line model is based on Marti's time domain formulation which is adopted in the EMTP and EMTDC programs. Improvements to speed up the calculation are made in order to realize electromagnetic transient simulation in real-time by parallel processing using two digital signal processors (DSPs) for each line. 41 /spl mu/s and 71 /spl mu/s time steps are readily achieved in real time with the new line model for three phase and double circuit (6 conductors) transmission lines respectively, The new line model is now installed in a real-time digital simulator (RTDS). Field test results are presented in this paper for validating the new line model.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.