Abstract

In this paper the optimal energy efficiency and high pressure problem in single stage transcritical carbon dioxide vapour compression units is addressed. A real-time model-based optimisation algorithm for the optimal (or quasi-optimal, close to the optimal) pressure determination is developed as a more efficient and robust solution than literature approximated ones. The problem is solved by a model estimating the system performance and by measuring its boundary conditions. The model is obtained by an on-line artificial neural network identification technique and the optimisation problem is worked out by a particle swarm technique. The proposed algorithm is dynamically tested by simulation, considering the performance of a supply water temperature controlled carbon dioxide heat pump. It appears to successfully approximate the optimal cycle discharge pressure showing an average daily pressure deviation of 0.9×105Pa over a two years simulation period, corresponding to 1.1% increase in the cumulated energy consumption, compared to the optimal pressure solution.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.