Abstract

In order to examine the ultimate high-voltage interruption ability of a vacuum interrupter, a particle in cell-Monte Carlo collision computer simulation was conducted under the following conditions. Residual charged and neutral particles at current zero were arranged between the electrodes. The particle conditions were obtained from an extrapolated value of experimental data. Secondary electron emission and self-sputtering effects due to ion bombardment were also considered for the simulation. The simulation voltage, which also represents the recovery voltage, was applied between the electrodes. From the results of a simulation on a 168-kV/25-kA 40-mm-diameter one-break interrupter, it was found that the breaking ability is most influenced by the initial neutral particle density. The charged particle density and the secondary electron emission coefficient were found to have a lesser effect on the breaking capability. Consequently, it is estimated that the self-sputtering coefficient from ion bombardment is one of the most important parameters for metal vapor supply after current zero.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.