Abstract

Various commercially available natural ventilation devices supply fresh air without mechanical assistance. These devices offer a low-energy alternative to mechanical air handling units. However, they often cannot satisfy recommended ventilation rates due to their dependence on both macro- and microclimate wind speeds. This work examines the feasibility of achieving the recommended fresh air delivery rates without impacting on the device energy requirements. A numerical investigation is carried out using a standard passive stack device geometry combined with a simulated low-powered axial fan. The investigation shows that a low-induced pressure of 20 Pa is enough to satisfy the legislative requirements. Depending on the macroclimate conditions, this induced pressure could be generated from a commercially available solar-powered system. As the fan system is only used in periods of low external wind velocities (1 m/s), it is termed a passive-assisted stack.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.