Abstract
This paper proposes a novel preventive frequency stability constrained optimal power flow analysis in a power system model with a wind farm. As for the frequency stability analysis, the loss of the total wind power output is simulated considering the most severe wind output fluctuation scenario. Primary frequency response of the system after the wind power output loss is investigated by time-domain simulation approach. As the frequency stability constraint, the system frequency deviation after the wind output variation is constrained within a permissible range. In IEEE 39-bus system, the relationships between the capacities of the wind farm and the frequency deviations are analyzed. The influence of the frequency stability constraint on generator scheduling results is discussed.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.