Abstract

AbstractCurrent transformers (CTs) are widely used for energy metering, relay protection, condition monitoring and control circuits. However, CT saturation may lead to non‐negligible measurement errors and relay malfunctions, posing a threat to the stability and security of the power grid. In order to address the problem of CT saturation, a novel measurement‐protection‐integrated current transformer (MPICT) is proposed. First, the working states of the MPICT are summarised and the approximate expressions for the steady‐state measuring characteristics, the transient response characteristics, and the measurement errors are derived from the equivalent circuit model. Then, the feasibility of the MPICT and the theoretical analyses are verified by the 3D FEM simulation imitating the presented MPICT excited by diverse currents. Finally, a down‐scale prototype is fabricated and a series of tests are conducted in the laboratory to validate the effectiveness of the equipment. The simulation and experimental results suggest that the output of the MPICT can accurately reconstruct the primary current waveform, even if the primary current contains decaying or constant DC component.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call