Abstract
HVDC transmission system is becoming increasingly desirable for its obvious technical and environmental advantages. A novel single-end distance protection scheme for HVDC lines is proposed in this paper. It is based on the linear distribution of low frequency voltage signals between the relay point and setting point. An internal fault can be detected if the low-pass filtered measure voltage is opposite in sign with the compensating voltage at the setting point, which can be calculated with the R-L differential-equation algorithm. To find a tradeoff between operating speed and accuracy, the protection is divided into K zones, each of which has different protection scopes and cut-off frequencies. A two-terminal HVDC system and a multi-infeed HVDC system are respectively built in EMTDC. Comprehensive simulation results have indicated that the proposed protection scheme has satisfactory operation performance and will be not influenced by system topologies or parameters. Besides, it is not sensitive to noises or voltage levels. Compared with many other single-end protections for HVDC lines, this novel distance protection has clear setting principles, lower sampling frequency, smaller calculation amount and faster operating speed.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: International Journal of Electrical Power & Energy Systems
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.